HB-JDW352 Overhead Line Ground Fault Locator
Integrated fault diagnosis, AC location, DC location, AC withstand voltage, and DC withstand voltage functions
Automatically suggests an appropriate location method
Line insulation resistance and capacitance measurement
Signal reception: segment search along the line, no need to climb poles to connect sensors
No need to disconnect the line grounding PT
All-in-one location mode, especially solving the problem of arc grounding location
Acceptance testing after fault repair
The transmitter has automatic discharge stop, overcurrent protection, and overheating protection functions to ensure operational safety. The transmitter is equipped with a high-capacity lithium-ion battery pack for convenient portability
Aerial line fault locator, suitable for locating faults on aerial lines with voltage ranging from 6 to 35kV. It can address various types of faults, including low-resistance faults, high-resistance faults, arc grounding faults, and inter-phase short circuit faults. It provides a complete set of solutions for aerial line fault location, integrating four functions: fault diagnosis, AC location, DC location, DC withstand voltage testing, and AC withstand voltage testing. The innovative AC location mode can detect characteristic signals directly under the line without the need to climb poles and attach sensors, featuring simple operation and convenient use. For high-resistance faults occurring on lines equipped with smart switches (with grounding PT), it uses an AC location combined with a step-up transformer, eliminating the need to remove the PT. The transmitter is equipped with a large-capacity lithium battery, making it convenient for use and portability.
Specifications
- Working Mode
- Fault Diagnosis, AC Location, DC Location, AC Withstand Voltage, DC Withstand Voltage
- Display Mode
- 800x480 High Brightness Color LCD Display
- Power Supply
- Built-in 480WH Lithium Battery Pack
- Charger Power Supply
- Input: AC220V 50~60Hz Output: 54.6V, 2A
- Weight
- 13kg
- Resistance Measurement
- Range: 600MΩ Accuracy: ±10%
- Capacitance Measurement
- Range: Maximum 10uF Accuracy: ±20%
Contact Us