HB-SD810 Cable Comprehensive Online Monitoring System Cable Tunnel Comprehensive Online Monitoring Device
Real-time online monitoring. The cable integrated online monitoring system can perform real-time 24-hour continuous monitoring of the cable joints at the monitored location.
Multiple different principle testing methods are combined to improve the reliability of the system's diagnostic results. This system adopts three testing methods: partial discharge, grounding current, and temperature, which facilitates the timely detection of insulation hazards in the joints.
The system software can display data from dual optical cameras.
The Cable Joint Comprehensive Online Monitoring System is suitable for online monitoring of partial discharge, grounding current, and temperature of cable joints rated from 6kV to 500kV. It can display the amplitude and frequency of partial discharge, as well as current and temperature data in real time, and provide an intuitive display of temperature imaging information. It can determine the relative position of the discharge point, issue alarms when necessary, and store test spectra, discharge trends, and temperature images, thereby enabling timely detection of insulation defects in cable joints and providing criteria for evaluating their insulation level and aging degree, thus offering a basis for cable maintenance work.
Minimum measurable discharge amplitude of the system: 2pC; the frequency range of the pulse current sensor is 1M~100MHz; the measurement range of the current transformer is 0~300A; the sensitivity of the temperature sensor is ±0.5℃, with a temperature measurement range of -55℃~+125℃; the dual-light camera uses thermal imaging and visible light technology, with a temperature measurement accuracy of ±2℃ or 2% of the reading.
The system adopts comprehensive anti-interference measures such as analog filtering, pulse grouping, periodic pulse elimination, dynamic threshold setting, and phase window opening, ensuring the reliability of the test data.
Specifications
- Scope of Application
- 6kV~500kV Cable
- Sensor Types
- High-frequency Pulse Current Sensor, Power Frequency Phase Transformer, Current Transformer, Temperature Sensor and Dual Light Camera
- Partial Discharge
- 2pC~10000pC
- Grounding Ring Current
- 0~300A
- Temperature
- -55℃~+125℃
- Data Acquisition Mode
- Timed Acquisition (Acquisition Interval Can Be Configured)
- Data Transmission Interval
- 30min (Transmission Interval Can Be Adjusted)
- Baud Rate
- 9600/115200bps
- Power Supply Method
- AC220V/CT Power Take-off
- Communication Method
- 4G
- Communication Protocol
- Modbus-RTU Protocol
- Protection Level
- ≥IP65
- Ambient Temperature
- -25ºC~+70ºC
- Altitude
- ≦4500m
- Sensor Principle
- Rogowski Coil Principle
- Detection Range
- 2pC~100000pC
- Sensitivity
- 2pC
- Matching Impedance
- 50Ω
- Operating Frequency Band
- 1~100MHz
- Transmission Method
- Coaxial Cable
- Connector Type
- TNC
- Protection Rating
- IP68
- Dimensions
- 29mm~116mm (Customizable)
- Installation Position
- Cable Connector Grounding Wire
- Installation Method
- Clamp-type, Snap-on
- Environmental Temperature
- -55ºC~+85ºC
- Altitude
- ≦4500m
- Sensor Principle
- Rogowski Coil Principle
- Detection Range
- 1A~100KA
- Sensitivity
- 85mV/KA@50Hz
- Coil Resistance
- 50~250Ω
- Internal Resistance Temperature Drift Coefficient
- Un-calibrated 200ppm/℃ measured; Calibrated 50ppm/℃
- OA Output (Zero Drift)
- ≦0.1mv
- Phase Difference
- ≦0.5
- Linearity
- ±0.2%
- Bandwidth
- 1Hz~50kHz (-3dB)
- Protection Class
- IP68
- Dimensions
- Circumference 420mm, Inner Diameter 120mm; Circumference 620mm, Inner Diameter 180mm
- Installation Position
- Cable body
- Installation method
- Snap-fit installation
- Environmental temperature
- -30℃~80℃
- Altitude
- ≦4500m
- Installation type
- Clamp type, opening and closing style
- Turns ratio
- 1000:1
- Accuracy
- 0.5 class
- Rated secondary load
- 4Ω
- Enclosure material
- ABS
- Secondary side short-time power frequency withstand voltage
- 3000V/min
- Inter-turn insulation resistance of winding
- 1000MOhms@500Vdc
- Operating environmental temperature
- -30℃~70℃
- Operating environmental humidity
- <80%RH
- Measurement range
- -55℃~+125℃
- Sensitivity
- ±0.5℃
- Power supply method
- 3~5V/DC
- Protection rating
- IP68
- Dimensions
- 20*7.5*3.5mm
- Installation location
- High-voltage cable intermediate joint
- Installation method
- Adhesive and bundling
- Environmental temperature
- -25ºC~+70ºC
- Altitude
- ≦4500m
- Pixel
- 32*32
- Measurement method
- Thermal sensor
- Power supply
- 5-12V DC
- Measured temperature
- 10~50 degrees Celsius
- Field of view
- 33°*33°
- Operating temperature
- -40~85 degrees Celsius
- Communication port
- RS485
- Power consumption
- <1W
- Operating temperature
- -20~50℃
- Working humidity environment
- 15-70%RH
- Pressure range
- Standard atmospheric pressure ±10﹪
- External dimensions
- 110×50×30mm3
- Measurement range
- CO :(0-1000)ppm ; H2S:(0-100)ppm ;O2 :(0-30)%VOL; CH4:(0-100)%LEL
- Resolution
- CO :1ppm; H2S:1ppm ;O2 :0.1%VOL; CH4:1%LEL
- Working voltage
- (3.5~5)V
- Working current
- <100mA
- Response time
- <30s
- Output Method
- UART Output (2.8V Level)
- Operating Temperature
- -20 ºC~50ºC
- Operating Humidity
- 15%RH~90%RH
- Storage Temperature
- 0 ºC~20ºC (Recommended)
- Expected Lifespan
- 2 Years (In Normal Air)
- Measurement Range
- 0~5m
- Measurement Resolution
- 0.1cm
- Measurement Accuracy
- 0.2 Class
- Operating Power Supply
- Battery Powered
- Means of communication
- ZigBee/RS485
- Protection level
- IP68
- Installation method
- Wall-mounted
- Operating voltage
- DC3.6V
- Detected gas
- Propane, smoke
- Response time
- ≤20 seconds
- Output signal
- TTL level
- Operating temperature
- 0℃~+50℃
- Storage temperature
- -20℃~70℃
- Vibration direction
- X\Y\Z tri-axial
- Acceleration range
- ±25g (other ranges can be customized)
- Acceleration frequency range
- 0.2-3000Hz
- Measurement accuracy
- ±0.5%×F·S (RMS)
- Velocity frequency response
- 10-1000Hz
- Velocity range
- 35mm/s
- ADC
- 16bit
- Sampling frequency
- 20kHz
- Sampling interval
- 1 minute-24 hours, adjustable
- Sampling time
- 5 seconds
- Output signal
- Acceleration
- Range
- -40~105℃
- Power supply
- 3.6V battery power
- Continuous working time
- Real-time acquisition and sampling interval can be set
- Communication method
- Lora 433
- Maximum transmission power
- 20dB
- Communication distance
- 1km (in open area)
- Weight
- Under 200g
- Temperature accuracy
- ≤±0.5℃
- Temperature stability
- <0.1℃/year
- Operating Temperature
- -40℃ to 70℃
- Operating Humidity
- Less than 95%RH
- Protection Rating
- IP68
Contact Us